UPS 3330ST TESCOM TEOS 400E PRO 30KVA/30KW NEW
Is expected
- Code
- 0.502.136
- Category
- Tescom UPS
- Rated Voltage
- 380 / 400 / 415 Vac (L-L)
- Voltage range
- 304~478Vac (L-L), full load 228V~304Vac (L-L), load decrease linearly according to the min phase voltage
- Rated frequency
- 50 / 60 Hz (auto-sensing)
- Frequency range
- 40 ~ 70 Hz
- Power factor
- > 0.99Total Harmonic Distortion (THDi) <3% (full linear load)
- Rated Voltage
- 380 / 400 / 415 Vac (L-L)
- Voltage Regulation
- = +- 1% (full linear load)
- Frequency
- Synchronized with utility in mains mode, 50/60 Hz ±0.1% in battery mode
- Waveform
- Sinusoidal
- Power factor
- 1
- Harmonic Distortion
- <1% (full linear load) <3% (full non-linear load according to IEC/EN62040-3)
- Current Crest Ratio
- 3:1
- Overload
- <110%, 60min, 110%~125%, 10min; 125%~150%,1min, >150%, 200ms
- Bypass voltage range
- Selectable, default -20%~+15% Up limited: +10%, +15%, +20%, +25%; Down limited: -10%, -15%, -20%, -30%, -40%
- Bypass frequency range
- Selectable, + - 1Hz, + - 3Hz, + - 5Hz
- Bypass overload
- 125%: long term operation; 125%~130%: 10min; 130%~150%: 1min; 150%~400%: 1s; >400%, less than 200ms
- DC voltage
- 120 ~ 240 Vdc settable
- Charging current
- 10A Max
- Recharge time
- 90% capacity restored in 8 hours
- Charger voltage precision
- 1%
- Inbuilt battery
- N/A
- Efficiency
- 95% Max
- Transfer time
- 0 ms
- Protections
- Short-circuit, output overload, overtemperature, battery low voltage, overvoltage / undervoltage and fan failure
- Max. number of parallel connections
- 4
- Communications
- RS232, USB, RS485, EPO, Dry contacts, Parallel port (Standard) SNMP card, WI-FI card, GPRS card, SMS alarms (Optional)
- Display
- LED + 5 inches LCD touch screen
- Operating temperature
- 0C ~ 40C
- Storage temperature
- Min 40 C Under Zero ~ 70 B360C (B360without battery)
- Relative humidity
- 0 ~ 95% (non-condensing)
- Altitude
- <1000m, load derated 1% per 100m from 1000 ~ 2000m
- IP rating
- IP 20
- Noise level at 1 m
- 58dB 100% load, 55dB 50% load
- Dimensions (mm)
- 250 x 840 x 930
UPS 3320ST TESCOM TEOS 400EB PRO 20KVA/20KW NEW
Is expected
- Code
- 0.502.138
- Category
- Tescom UPS
- Rated Voltage
- 380 / 400 / 415 Vac (L-L)
- Voltage range
- 304~478Vac (L-L), full load 228V~304Vac (L-L), load decrease linearly according to the min phase voltage
- Rated frequency
- 50 / 60 Hz (auto-sensing)
- Frequency range
- 40 ~ 70 Hz
- Power factor
- > 0.99Total Harmonic Distortion (THDi) <3% (full linear load)
- Rated Voltage
- 380 / 400 / 415 Vac (L-L)
- Voltage Regulation
- = +- 1% (full linear load)
- Frequency
- Synchronized with utility in mains mode, 50/60 Hz ±0.1% in battery mode
- Waveform
- Sinusoidal
- Power factor
- 1
- Harmonic Distortion
- <1% (full linear load) <3% (full non-linear load according to IEC/EN62040-3)
- Current Crest Ratio
- 3:1
- Overload
- <110%, 60min, 110%~125%, 10min; 125%~150%,1min, >150%, 200ms
- Bypass voltage range
- Selectable, default -20%~+15% Up limited: +10%, +15%, +20%, +25%; Down limited: -10%, -15%, -20%, -30%, -40%
- Bypass frequency range
- Selectable, + - 1Hz, + - 3Hz, + - 5Hz
- Bypass overload
- 125%: long term operation; 125%~130%: 10min; 130%~150%: 1min; 150%~400%: 1s; >400%, less than 200ms
- DC voltage
- 120 ~ 240 Vdc settable
- Charging current
- 10A Max
- Recharge time
- 90% capacity restored in 8 hours
- Charger voltage precision
- 1%
- Inbuilt battery
- (20+20) x 9AH, + -240VDC
- Efficiency
- 95% Max
- Transfer time
- 0 ms
- Protections
- Short-circuit, output overload, overtemperature, battery low voltage, overvoltage / undervoltage and fan failure
- Max. number of parallel connections
- 4
- Communications
- RS232, USB, RS485, EPO, Dry contacts, Parallel port (Standard) SNMP card, WI-FI card, GPRS card, SMS alarms (Optional)
- Display
- LED + 5 inches LCD touch screen
- Operating temperature
- 0C ~ 40C
- Storage temperature
- Min 40 C Under Zero ~ 70 B360C (B360without battery)
- Relative humidity
- 0 ~ 95% (non-condensing)
- Altitude
- <1000m, load derated 1% per 100m from 1000 ~ 2000m
- IP rating
- IP 20
- Noise level at 1 m
- 58dB 100% load, 55dB 50% load
- Dimensions (mm)
- 250 x 800 x 700
UPS 3120ST TESCOM TEOS 200 PRO 20KVA/20000W TOWER LCD NEW
Is expected
- Code
- 0.502.128
- Category
- Tescom UPS
- Nominal Voltage
- 3 x 400 VAC (3Ph+N)
- Voltage range
- 110-300 VAC 50% load 176-276 VAC 100% load
- Frequency range
- 46~54 Hz or 56~64Hz
- Power factor
- >= 0.99 @ 100% load
- Output Voltage
- 208/220/230/240VAC
- AC Voltage Regulation
- - + 1
- Frequency Range
- 46~54Hz or 56~64Hz
- Current Crest Ratio
- 3:1 (max.)
- Harmonic Distortion
- <= 2 % THD (Linear Load) <= 5 % THD (Non-linear Load)
- Transfer Time
- AC mode to Battery mode= Zero, Inverter to Bypass= Zero (when phase lock fails, <4ms interruption occurs from inverter to bypass)
- Waveform
- Pure Sine wave
- Overload
- 100-110% for 60 min, 110-125% for 10 min, 125%~150% 1min, >150% immediately
- AC Mode
- 95.5%
- ECO Mode
- 98.5%
- Battery Mode
- 94.5%
- Battery Type
- Depending on the capacity of external batteries
- Internal Battery Space
- N/A
- Charging Current
- 12A
- Charging Voltage
- 273 VDC + - 1% (Based on 20pcs bateries)
- LCD Panel
- color LCD
- Full Protection
- Overload, Over-temperature,Utility abnormal, UPS fault, UPS warning, battery low,etc
- Battery Mode
- Sounding every 4 seconds
- Low Battery
- Sounding every second
- Overload
- Sounding twice every second
- Fault
- Continuously sounding
- Standard Model Dimension, (mm)
- 626x 250 x 827
- Net Weight
- 46.5
- Operation Humidity
- 0-95 % RH 0- 40C (non-condensing)
- Noise Level
- Less than 65dB 1 Meter
- Smart RS-232/USB & Softwarel
- Supports Windows 2000/2003/XP/Vista/2008, Windows 7/8, Linux and MAC
UPS 3330ST TESCOM TEOS 400EB PRO 30KVA/30KW NEW
Is expected
- Code
- 0.502.139
- Category
- Tescom UPS
- Rated Voltage
- 380 / 400 / 415 Vac (L-L)
- Voltage range
- 304~478Vac (L-L), full load 228V~304Vac (L-L), load decrease linearly according to the min phase voltage
- Rated frequency
- 50 / 60 Hz (auto-sensing)
- Frequency range
- 40 ~ 70 Hz
- Power factor
- > 0.99Total Harmonic Distortion (THDi) <3% (full linear load)
- Rated Voltage
- 380 / 400 / 415 Vac (L-L)
- Voltage Regulation
- = +- 1% (full linear load)
- Frequency
- Synchronized with utility in mains mode, 50/60 Hz ±0.1% in battery mode
- Waveform
- Sinusoidal
- Power factor
- 1
- Harmonic Distortion
- <1% (full linear load) <3% (full non-linear load according to IEC/EN62040-3)
- Current Crest Ratio
- 3:1
- Overload
- <110%, 60min, 110%~125%, 10min; 125%~150%,1min, >150%, 200ms
- Bypass voltage range
- Selectable, default -20%~+15% Up limited: +10%, +15%, +20%, +25%; Down limited: -10%, -15%, -20%, -30%, -40%
- Bypass frequency range
- Selectable, + - 1Hz, + - 3Hz, + - 5Hz
- Bypass overload
- 125%: long term operation; 125%~130%: 10min; 130%~150%: 1min; 150%~400%: 1s; >400%, less than 200ms
- DC voltage
- 120 ~ 240 Vdc settable
- Charging current
- 10A Max
- Recharge time
- 90% capacity restored in 8 hours
- Charger voltage precision
- 1%
- Inbuilt battery
- "(15+15) x 9AHx 2 strings + -180VDC"
- Efficiency
- 95% Max
- Transfer time
- 0 ms
- Protections
- Short-circuit, output overload, overtemperature, battery low voltage, overvoltage / undervoltage and fan failure
- Max. number of parallel connections
- 4
- Communications
- RS232, USB, RS485, EPO, Dry contacts, Parallel port (Standard) SNMP card, WI-FI card, GPRS card, SMS alarms (Optional)
- Display
- LED + 5 inches LCD touch screen
- Operating temperature
- 0C ~ 40C
- Storage temperature
- Min 40 C Under Zero ~ 70 B360C (B360without battery)
- Relative humidity
- 0 ~ 95% (non-condensing)
- Altitude
- <1000m, load derated 1% per 100m from 1000 ~ 2000m
- IP rating
- IP 20
- Noise level at 1 m
- 58dB 100% load, 55dB 50% load
- Dimensions (mm)
- 250 x 840 x 930
UPS 3360ST TESCOM TEOS 400 60KVA/60KW 3/3 LCD ( 3L NEW
Is expected
- Code
- 0.502.133
- Category
- Tescom UPS
- Voltage
- 100 / 110 / 120 V: 80 - 150 Vac, 220 / 230 / 240 V: 162 - 295 Vac (145 - 295 Vac optional)
- Frequency
- 50 / 60 Hz + - 10% (auto-sensing)
- Voltage
- 100 / 110 / 120 Vac + - 10% or 220 / 230 / 240 Vac + - 10%
- Frequency
- 50 / 60 Hz + - 1% (auto-sensing)
- Waveform
- Mains mode: pure sine wave Battery mode: simulated sine wave
- Transfer time
- Typical 2 - 7 ms, 10 ms max.
- DC voltage
- 24 V
- Configuration
- 12 V / 9 Ah x 2
- Recharge time
- 6 - 8 h
- USB (optional)
- Supports Windows? 98 / 2000 / 2003 / XP / Vista / 2008 / Windows?7 / 8 / 10
- Protections
- Short circuit - battery overcharge - overdischarge - overload - surge
- Humidity
- 20 - 90% RH @ 0- 40 (non-condensing)
- Noise level
- <= 40 dB (1 m)
- Metal Case